What’s corona discharge?

What Is the Corona Effect?

The corona effect is a phenomenon of partial electrical discharge caused by the ionization of the air surrounding a conductor. It appears when the voltage exceeds a critical value, but whose conditions do not allow the formation of an electric arc. A corona effect produces a glow of bluely light, which forms around the cables carrying high voltage current, more frequently on aerial power lines.

How Does a Corona Discharge Occur?

A corona discharge occurs when a direct or alternating current is created between two electrodes brought to a high potential and separated by a neutral fluid like air, by ionization of this fluid. A plasma is then created and the electric charges propagate by passing from the ions to the molecules of neutral gases.

When the electric field at a point of the fluid is large enough, the fluid ionizes around this point and becomes conductive. If the fluid is air, the ionization is responsible for the bluely light emitted.

How Do Conductor Shape and Electric Field Affect Corona Discharge?

In particular, if a charged object has points or corners, the electric field will be greater there than elsewhere leading to a corona discharge: the phenomenon will tend to stabilize itself since the ionized region becoming conductive, the tip will apparently tend to disappear. The charged particles then dissipate under the effect of the electric force and are neutralized on contact with an object of opposite charge. Corona discharges therefore generally occur between an electrode with a small radius of curvature, such as a defect in the conductor forming a point, and a another with a large radius of curvature such as a metal plate or the ground.

From Corona Discharge to Electric Arc

If the geometry of the conductor and the value of the field are such that the ionized region expands instead of stabilizing, the current may eventually find a path to the reverse electrode and creates sparks or electric arc.

 

Download your guide

 

Impact of Weather Conditions

The corona effect depends on the superficial electric field of the conductor, but also on its diameter, its surface condition and then the density and humidity of the surrounding air. Indeed, when it is raining or under very humid conditions1, an aerial power line starts to vibrate at the natural frequency of the conductor in light winds on high voltage lines when drops of water are suspended under the conductors in rainy, wet snow or heavy fog2 or the presence of drops of water suspended on the underside of a cable3; the intermittent presence of the space charge4,5,6 and of the ionic wind located in the immediate vicinity of the drops of water suspended from the conductor are the main causes of this phenomenon2, the magnitude and location of which will depend on several parameters such as value and polarity of the electric field on the surface of the conductor, intensity of precipitation, speed of the transverse wind2,7.

Impact on High Voltage Lines

This effect is not desired on power lines since it causes power loss for the network. In addition to unpleasant crackles emitted by that phenomenon, the corona effect can interfere with radio and television signals. It also creates vibration on the power lines, which, combined with vibrations due to wind8, reduces the lifetime of power lines, accelerating aging of the conductor and wear of its anchor points and leading to an inevitable and more important corona effect. Dioxygen in the air is also transformed into ozone, which is a harmful gas for exposed animals living nearby.

Advanced Imaging Solutions for Power Line Inspection

Detecting Corona Discharge with SUV Imaging

Exosens offers advanced imaging solutions to detect corona discharge in high voltage power lines with SUV solutions. Exosens SUV (iNocturn SUV) solutions are based on the coupling of image intensifier and a CMOS high performance detector for high precision corona discharge detection.

Detecting Heat-Related Power Line Defects with LWIR Imaging

Exosens offers advanced imaging solutions to detect power line defects with LWIR solutions. Exosens LWIR cameras and cores consists of SWaP features and are available in industry standard interfaces of MIPI CSI-2, USB and UVC for power line defect detection.

Ask one of our Expert for advice

 

Frequently Asked Questions About Corona Discharge

What is a corona discharge?

A corona discharge is a partial electrical discharge caused by the ionization of the air surrounding a conductor. It occurs when the voltage exceeds a critical value without creating a complete electric arc.

What causes corona discharge?

Corona discharge occurs when the electric field around a conductor becomes strong enough to ionize the surrounding air. The likelihood of discharge depends on factors such as voltage, conductor shape, surface condition, air density and humidity.

Why does corona discharge produce a blue glow?

The blue glow appears when the surrounding air becomes ionized by a sufficiently strong electric field. This ionization creates a conductive region around the conductor and emits visible light.

Where does corona discharge usually occur?

Corona discharge commonly occurs around conductors carrying high-voltage current, particularly on overhead power lines. It is more likely to form near sharp points, corners or defects where the electric field is concentrated.

Can corona discharge create an electric arc?

Yes. If the ionized region continues to expand instead of stabilizing, the current may find a path to an electrode of opposite polarity and produce sparks or an electric arc.

How do weather conditions affect corona discharge?

Rain, wet snow, heavy fog and high humidity can increase corona activity. Water droplets suspended beneath a conductor can also contribute to corona-induced vibration on high-voltage power lines.

What are the effects of corona discharge on power lines?

Corona discharge can cause power loss, audible crackling, interference with radio and television signals, and vibrations that contribute to conductor aging and wear at anchor points.

Does corona discharge produce ozone?

Yes. Corona discharge can transform oxygen in the air into ozone. At sufficient concentrations, ozone can be harmful to animals and other living organisms exposed nearby.

 

Explore further below to learn more about corona-discharge, our technology, benefits, and our cutting-edge solutions:

https://www.exosens.com/news/corona-discharges-detection

https://www.exosens.com/news/ultraviolet-uv-and-thermal-cameras-high-tech-solutions-corona-discharges

https://www.exosens.com/news/high-voltage-line-maintenance-which-solutions

https://www.exosens.com/applications/powergrid-maintenance

 

 

References

1 M.Farzaneh, "Effects of the intensity of precipitation and transverse wind on the corona induced vibration of HV conductors", IEEE, Vol. 7, No. 2, April 1992

2 Gourbi, Abdelkader (2008) Mécanisme des vibrations induites par effet de couronne ; Université Djillali Liabes de Sidi bel Abbes - Magister 2008

3 Akazaki M (1965), "Corona phenomena from water drop on smooth conductors under high direct voltage", IEEE, Janvier 1965

4 Carl Potvin, " Comportement et effet de la charge d'espace sur le mécanisme des vibrations induites par effet de couronne ", Mémoire comme exigence partielle de la maîtrise en ingénierie, université de Chicoutimi, Canada, mars 2000.

5 Farzaneh M & Teisseyre Y (1988), "Mechanical vibration of HV conductors induced by corona: roles of the space charge and ionic wind", IEEE, VOL, 3, 3 July 1988

6 Farzaneh M & Phan LC(1985) "On the Role of the Space Charge Produced by Hanging Water Drops in the Mechanism of the Corona-Induced Vibration of H.V. Conductor", J. of electrostatics, Vol. 17, pp. 235-244

7 Myriam Hamel, "Influence de la variation de la température ambiante sur les vibrations induites par effet de couronne", Mémoire comme exigence partielle de La maîtrise en ingénierie, université de Chicoutimi Canada, août 1991.

8 Sayah H, Brahami m, Bendaoud A & Rahli M (2004) "Vibrations éoliennes des câbles aériens", La 1re Conférence Nationale sur l’Électrotechnique et ses Applications, Sidi Bel-Abbès, Algérie, Mai 2004.

 A & Rahli M (2004) "Vibrations éoliennes des câbles aériens", La 1re Conférence Nationale sur l’Électrotechnique et ses Applications, Sidi Bel-Abbès, Algérie, Mai 2004.